Fire Safety
ALL CLEAR
SS
ALL CLEAR โ€” Tidak Ada Alarm Kebakaran Aktif
32
Zona Normal
0
Zona Alarm
1
Trouble
4/4
FM-200 Ready
3/3
VESDA Clear
FACP โ€” Zona Proteksi (32 zona)
Notifier NFS-320 ยท โ€”
๐Ÿข
Z01 - Server Hall A
Normal
๐Ÿข
Z02 - Server Hall B
Normal
โ„๏ธ
Z03 - Cooling Room
Normal
โšก
Z04 - UPS Room A
Normal
โšก
Z05 - UPS Room B
Normal
๐Ÿ”ง
Z06 - Genset Room
Normal
๐Ÿ–ฅ๏ธ
Z07 - NOC Room
Normal
๐Ÿ“ฆ
Z08 - Storage Room
Trouble
+24 zona lainnya ยท semua Normal ยท Lihat semua โ†’
FM-200 Status
FM-SH-A
Server Hall A
Ready
FM-SH-B
Server Hall B
Ready
FM-UPS-A
UPS Room A
Ready
FM-UPS-B
UPS Room B
Ready
VESDA Status
VESDA-SH-A
0.008 %/m
Clear
VESDA-SH-B
0.005 %/m
Clear
VESDA-UPS-A
0.012 %/m
Clear
Event Terkini
WaktuZonaSistemEventDurasiStatus
2026-03-01 03:22Z08 - StorageFACPPanel Trouble - Detector DisconnectOngoingTrouble
2026-02-20 14:15Z01 - SH-AVESDAAuthorized Test - Aerosol Commissioning12 menitResolved
2026-02-10 09:00All ZonesFACPMonthly Test - Panel Self Test5 menitResolved
2026-01-28 19:42Z04 - UPS-AFACPFalse Alarm - Dust Particle3 menitResolved
32
Total Zona
Notifier NFS-320
31
Zona Normal
1
Trouble
Z08 - Storage Room
0
Alarm Aktif
0
Disabled
Trouble: Z08 โ€” Storage Room
Detector disconnect sejak 2026-03-01 03:22 ยท Teknisi telah dinotifikasi ยท Estimasi perbaikan: hari ini
Ongoing
Semua Zona (32)
Detail Zona per Area
ID ZonaNama ZonaAreaLantaiDetectorPanelStatus
Z01Server Hall A - Row A/BData Hall18 Smoke + 2 HeatPanel-01Normal
Z02Server Hall B - Row C/DData Hall18 Smoke + 2 HeatPanel-01Normal
Z03Cooling Room CRACMechanical14 Smoke + 1 HeatPanel-01Normal
Z04UPS Room AElectrical16 Smoke + 2 HeatPanel-01Normal
Z05UPS Room BElectrical16 Smoke + 2 HeatPanel-01Normal
Z06Generator RoomMechanicalB14 Smoke + 4 HeatPanel-02Normal
Z07NOC RoomOffice14 SmokePanel-01Normal
Z08Storage RoomSupport14 Smoke (-1 disconnect)Panel-01Trouble
+24 zona lainnya ยท semua Normal
3
Unit VESDA
Xtralis VESDA-E VEA
3
Status Clear
0.008
Max Level (%/m)
SH-A ยท Threshold: 0.05
364
Hari Bebas Event
VESDA-SH-A โ€” Server Hall A
ClearXtralis VESDA-E VEA ยท 4 Sampling Pipe
Level Deteksi per Pipe
Pipe 1 โ€” Row A (top)0.008 %/m
Pipe 2 โ€” Row A (mid)0.006 %/m
Pipe 3 โ€” Row B (top)0.007 %/m
Pipe 4 โ€” Row B (mid)0.005 %/m
Threshold & Konfigurasi
Alert Level0.050 %/m
Action Level0.100 %/m
Fire 10.200 %/m
Fire 20.500 %/m
Inspeksi terakhir: 10 Feb 2026
Inspeksi berikutnya: 10 Mei 2026
VESDA-SH-B โ€” Server Hall B
ClearXtralis VESDA-E VEA ยท 4 Sampling Pipe
Pipe 1 โ€” Row C (top)0.005 %/m
Pipe 2 โ€” Row C (mid)0.004 %/m
Pipe 3 โ€” Row D (top)0.006 %/m
Pipe 4 โ€” Row D (mid)0.003 %/m
VESDA-UPS-A โ€” UPS Room A
ClearXtralis VESDA-E VEA ยท 2 Sampling Pipe
Pipe 1 โ€” Battery Area0.012 %/m
Pipe 2 โ€” UPS Inverter0.009 %/m
UPS room memiliki threshold lebih sensitif: Alert 0.03 %/m karena risiko off-gassing baterai
Trend Level Asap 24 Jam Terakhir
Semua Sistem FM-200 Siap โ€” Ready to Discharge
4 sistem aktif ยท Tekanan semua silinder normal ยท Tidak ada riwayat discharge darurat
FM-SH-A
Server Hall A ยท Novec 1230
Ready
TEKANAN SILINDER
42.1 bar
AGENT WEIGHT
48.2 kg
LUAS AREA
250 mยฒ
KONSENTRASI
6.25%
Tekanan Silinder42.1 / 45 bar
Inspeksi terakhir: 15 Jan 2026
Inspeksi berikutnya: 15 Apr 2026
Mode: Automatic
FM-SH-B
Server Hall B ยท Novec 1230
Ready
TEKANAN SILINDER
43.5 bar
AGENT WEIGHT
48.2 kg
LUAS AREA
250 mยฒ
KONSENTRASI
6.25%
Tekanan Silinder43.5 / 45 bar
Inspeksi terakhir: 15 Jan 2026
Inspeksi berikutnya: 15 Apr 2026
Mode: Automatic
FM-UPS-A
UPS Room A ยท Novec 1230
Ready
TEKANAN SILINDER
41.8 bar
AGENT WEIGHT
32.4 kg
LUAS AREA
120 mยฒ
KONSENTRASI
6.25%
Tekanan Silinder41.8 / 45 bar
Inspeksi terakhir: 15 Jan 2026
Inspeksi berikutnya: 15 Apr 2026
Mode: Automatic
FM-UPS-B
UPS Room B ยท Novec 1230
Ready
TEKANAN SILINDER
44.0 bar
AGENT WEIGHT
32.4 kg
LUAS AREA
120 mยฒ
KONSENTRASI
6.25%
Tekanan Silinder44.0 / 45 bar
Inspeksi terakhir: 15 Jan 2026
Inspeksi berikutnya: 15 Apr 2026
Mode: Automatic
Riwayat Discharge & Inspeksi
TanggalSistemTipeKeteranganTeknisiHasil
15 Jan 2026SemuaInspeksiQuarterly pressure check & weight verificationPT Servochem IndonesiaPass
15 Okt 2025SemuaInspeksiQuarterly pressure check & weight verificationPT Servochem IndonesiaPass
20 Feb 2025FM-SH-ARefillAgent refill setelah discharge test commissioningPT Servochem IndonesiaComplete
16
Total Channel
14
Channel Aktif
2
Channel Spare
0
Alarm Aktif
DI Card โ€” 16 Channel Status
Modul Digital Input ยท FACP Interface
CH01
NORMAL
Fire Zone 1
CH02
NORMAL
Fire Zone 2
CH03
NORMAL
Fire Zone 3
CH04
NORMAL
Fire Zone 4
CH05
READY
FM-200 SH-A
CH06
READY
FM-200 SH-B
CH07
READY
FM-200 UPS-A
CH08
READY
FM-200 UPS-B
CH09
DRY
Water Leak 1
CH10
DRY
Water Leak 2
CH11
CLOSED
Door Zone A
CH12
CLOSED
Door Zone B
CH13
OPEN
Damper HVAC
CH14
STANDBY
Evac Bell
CH15
โ€”
Spare
CH16
โ€”
Spare
Konfigurasi Channel
CHNamaFungsiTipe InputLogicKondisi NormalStatus
CH01Fire Zone 1FACP Zone MonitorDry Contact NONormal OpenOpen / DRYNormal
CH02Fire Zone 2FACP Zone MonitorDry Contact NONormal OpenOpen / DRYNormal
CH05FM-200 SH-ASuppression FeedbackDry Contact NCNormal CloseClose / READYNormal
CH09Water Leak 1Leak DetectionResistiveResistance >1kฮฉDry (No Leak)Normal
CH11Door Zone AAccess Control InterlockMagnetic SWNormally ClosedClosedNormal
CH13Damper HVACFire Damper StatusDry ContactOpen = NormalOpen (Run)Normal
CH15โ€”Spareโ€”โ€”โ€”Spare
CH16โ€”Spareโ€”โ€”โ€”Spare
0
Real Alarm (YTD)
2
False Alarm (YTD)
4
Test / PM (YTD)
247
Hari Bebas Alarm
Statistik Event per Bulan
Log Event Lengkap
WaktuZonaSistemTipeKeteranganDurasiTindakanStatus
2026-03-01 03:22 Z08 - StorageFACP Trouble Panel Trouble โ€” Detector Disconnect (1 unit) Ongoing Teknisi dinotifikasi Open
2026-02-20 14:15 Z01 - SH-AVESDA Test Authorized Test โ€” Aerosol commissioning VESDA-SH-A 12 menit Authorized, direset manual Resolved
2026-02-10 09:00 All ZonesFACP PM Test Monthly Panel Self-Test โ€” Scheduled PM by Notifier 5 menit Scheduled, auto-reset Resolved
2026-01-28 19:42 Z04 - UPS-AFACP False Alarm False Alarm โ€” Dust particle dari aktivitas maintenance UPS 3 menit Investigasi + reset + bersihkan Resolved
2026-01-10 09:00 All ZonesFACP PM Test Monthly Panel Self-Test 5 menit Scheduled, auto-reset Resolved
2025-12-15 22:11 Z06 - GensetFACP False Alarm False Alarm โ€” Asap knalpot genset saat test run bulanan 7 menit Investigasi + reset + prosedur diperketat Resolved