Cooling System
LIVE
RZ
21.4°C
Avg Supply Air
Return: 28.7°C · ΔT: 7.3°C
4.2
Avg Chiller COP
CHWS: 8.2°C / CHWR: 14.1°C
0.36
pCUE
720 kW Cooling / 2,000 kW IT
48
CRAC Running
48 unit · 0 Warning · 0 Fault
6
Chiller Active
720 kW total · 68% avg load
Thermal Map — Zone A (Row 1–10)
<20°C
>27°C
Temp Trend 24h
27.8°C
Max Supply
20.1°C
Min Supply
CRAC Status (48 unit)
Lihat semua →
UnitZonaSupply°CReturn°CΔTLoadStatus
CRAC-A01Zone A Row 120.828.27.4
65%
Normal
CRAC-A02Zone A Row 221.228.97.7
70%
Normal
CRAC-A07Zone A Row 727.835.27.4
88%
Warning
CRAC-B01Zone B Row 121.028.47.4
68%
Normal
+44 unit lainnya · Normal
Chiller Status
Lihat semua →
ChillerCHWS°CCHWR°CCOPLoadStatus
CH-018.013.84.462%Running
CH-028.214.14.268%Running
CH-038.113.94.371%Running
CH-048.314.24.165%Running
CH-058.414.44.074%Running
CH-068.214.04.270%Running
CRAC / CRAH Management
48 unit · Computer Room Air Conditioning/Handling · Protokol BACnet/Modbus
48
Total CRAC
47 Normal · 1 Warning · 0 Fault
21.4°C
Avg Supply
Setpoint: 21.0°C
28.7°C
Avg Return
ΔT rata-rata: 7.3°C
68%
Avg Load
Total: 720 kW / 1,056 kW
49%
Avg Humidity
Target: 45–55% RH
Daftar CRAC / CRAH (48 unit)
Update: 07/03/2026 14:32
Unit IDBrand/ModelZonaSupply°CReturn°CΔTRH%LoadSetpointModeStatus
CRAC-A01Stulz CyberAir · 22kWZone A20.828.27.448%
65%
21.0°CCoolingNormal
CRAC-A02Stulz CyberAir · 22kWZone A21.228.97.750%
70%
21.0°CCoolingNormal
CRAC-A03Emerson Liebert · 30kWZone A21.028.57.547%
62%
21.0°CCoolingNormal
CRAC-A04Schneider InRow · 20kWZone A21.429.17.751%
72%
21.0°CCoolingNormal
CRAC-A05Stulz CyberAir · 22kWZone A21.128.67.549%
67%
21.0°CCoolingNormal
CRAC-A06Emerson Liebert · 30kWZone A21.629.47.852%
75%
21.0°CCoolingNormal
CRAC-A07Stulz CyberAir · 22kWZone A27.835.27.452%
88%
21.0°CHigh LoadWarning
CRAC-B01Schneider InRow · 20kWZone B21.028.47.447%
68%
21.0°CCoolingNormal
CRAC-B02Emerson Liebert · 30kWZone B21.329.07.748%
71%
21.0°CCoolingNormal
CRAC-B03Stulz CyberAir · 22kWZone B20.928.37.446%
64%
21.0°CCoolingNormal
Menampilkan 10 dari 48 unit · Load lebih banyak →
Load Distribusi per Zone
Trend Supply / Return 24h
Chiller Plant
6 unit aktif · Total kapasitas 1,060 kW · Chilled Water System
6
Chiller Aktif
6 Running · 0 Standby · 0 Fault
4.2
Avg COP
Target ≥ 4.0 ✓
8.2°C
Avg CHWS
Setpoint: 8.0°C
14.1°C
Avg CHWR
ΔT: 5.9°C
720 kW
Total Cooling
68% dari 1,060 kW kapasitas
CH-01
Carrier 30XA · 180 kW · BACnet
Running
8.0°C
CHWS
13.8°C
CHWR
4.4
COP
62%
Load
111 kW
Output
25 kW
Power
Load62%
Run hours: 1,248 h · Next service: 252 h
CH-02
Carrier 30XA · 180 kW · BACnet
Running
8.2°C
CHWS
14.1°C
CHWR
4.2
COP
68%
Load
122 kW
Output
29 kW
Power
Load68%
Run hours: 986 h · Next service: 514 h
CH-03
Trane CGAM · 200 kW · Modbus
Running
8.1°C
CHWS
13.9°C
CHWR
4.3
COP
71%
Load
142 kW
Output
33 kW
Power
Load71%
Run hours: 2,104 h · Next service: 146 h ⚠
CH-04
Trane CGAM · 200 kW · Modbus
Running
8.3°C
CHWS
14.2°C
CHWR
4.1
COP
65%
Load
130 kW
Output
32 kW
Power
Load65%
Run hours: 1,782 h · Next service: 468 h
CH-05
Carrier 30XA · 150 kW · BACnet
Running
8.4°C
CHWS
14.4°C
CHWR
4.0
COP
74%
Load
111 kW
Output
28 kW
Power
Load74%
Run hours: 842 h · Next service: 658 h
CH-06
Carrier 30XA · 150 kW · BACnet
Running
8.2°C
CHWS
14.0°C
CHWR
4.2
COP
70%
Load
105 kW
Output
25 kW
Power
Load70%
Run hours: 620 h · Next service: 880 h
CHWS / CHWR Trend 24h
COP per Chiller
Thermal Map
Visualisasi distribusi suhu seluruh zona · 400 sensor · Update setiap 5 menit
21.4°C
Avg Supply
Min: 20.1°C · Max: 27.8°C
1
Hot Spot
CRAC-A07 zone · 27.8°C
398
Sensor Normal
dari 400 sensor aktif
2
Sensor Warning
Suhu > 25°C
Thermal Map — Zone A (Row 1–20 · 200 racks)
← Cold Aisle    Row 1 — Row 10 Row 11 — Row 20    Hot Aisle →
<20°C 20–22°C 22–25°C >25°C
Hot Spot Detection
LokasiSensorSuhuAmbangDurasiStatus
Zone A · Row 7 · Rack A-07CRAC-A07-sup27.8°C25.0°C3 jam 12 minWarning
Zone A · Row 10 · Rack A-10ENV-A10-r324.9°C25.0°C45 menitNear Limit
Zone B — semua dalam batas normal (< 23°C)
Suhu Hotspot Trend 24h
Cooling Analytics
Analisis efisiensi pendinginan · COP trend · Perbandingan beban · Rekomendasi optimasi
4.2
COP Hari Ini
Target ≥ 4.0 ✓ (+5%)
0.36
pCUE
Best: 0.32 · Target: <0.40
720 kW
Cooling Load
-8% vs kemarin
7.3°C
Avg ΔT CRAC
Target: 7–8°C ✓
Rp 2.4 jt
Biaya Cooling/hr
26% dari total biaya
COP Trend 30 Hari
Cooling Load vs IT Load
Efisiensi per Zona
Rekomendasi Optimasi AI
Naikkan setpoint CRAC Zone B ke 22°C
Suhu return Zone B rata-rata 27.1°C. Menaikkan setpoint bisa hemat ~18 kW (2.5%). Confidence: 87%
Rotasi Chiller CH-05 → Standby
Total cooling load 720 kW bisa ditangani 5 chiller. CH-05 masuk standby hemat 28 kW. Confidence: 74%
Service CRAC-A07 — Ganti filter
CRAC-A07 load 88% saat zona lain 65–72%. Filter kotor terdeteksi dari pola airflow. Jadwalkan PM.
Prediksi: IT load naik 12% minggu depan
Berdasarkan jadwal batch processing. Aktifkan CH-07 (standby) H-1 sebelum peak load. Confidence: 81%