Environment & Floor Plan
LIVE
RZ
▲ 2
126
Sensor Online
128 total · 2 offline
23.1°C
Avg Temperature
Max 26.8°C · Row A-04
48%
Avg Humidity
Max 72% · Row C-04
0
Water Leak
8/8 sensor dry
78%
Rack Utilization
31/40 rack terisi
Floor Plan — Data Hall Lantai 1
40 rack
Row A — Cold Aisle ←→ Hot Aisle
A01
A02
A03
A04
A05
CRAC
A06
A07
A08
A09
Row B
B01
B02
B03
B04
B05
CRAC
B06
B07
B08
B09
Row C
C01
C02
C03
C04
CRAC
C05
C06
C07
Row D
D01
D02
D03
D04
D05
CRAC
D06
D07
D08
D09
Normal
Warning
Critical
CRAC
Maintenance
Active Alerts
3
A09 — UPS Battery Low
Row A · 8 min ago
A04 — Temp Warning 26.8°C
Row A · 15 min ago
C04 — Humidity 72% RH
Row C · 22 min ago
Water Leak
All Clear
8/8 sensor dry
Environmental Sensor List
128 sensor · 126 online
Sensor IDRackPosisiTempHumidityTerakhir UpdateStatus
ENV-A01-TOPA01Top21.2°C46%5s laluNormal
ENV-A01-MIDA01Middle22.4°C48%5s laluNormal
ENV-A04-TOPA04Top26.8°C51%5s laluWarning
ENV-B07-MIDB07Middle25.3°C53%5s laluWarning
ENV-C04-MIDC04Middle24.2°C72%5s laluWarning
ENV-D09-BOTD09Bottom12m laluOffline
+122 sensor lainnya · Lihat semua →
26.8°C
Max Temperature
Rack A04 · Row A
23.1°C
Avg Temperature
Threshold: <25°C Normal
2
Hot Spot
A04 >25°C · B07 >25°C
48%
Avg Humidity
Target: 40–60% RH
1
Humidity Alert
C04 = 72% (High)
Avg Suhu per Row
Trend Suhu 1 Jam Terakhir
Heatmap Suhu — Data Hall
1
2
3
4
5
CRAC
6
7
8
9
<22°C
22–23°C
23–25°C
25–27°C
>27°C
CRAC
Kosong
Data Sensor Suhu & Humidity
Sensor IDRackRowPosisiSuhuHumidityMin SuhuMax SuhuStatus
ENV-A01-TOPA01ATop21.2°C46%20.8°C22.1°CNormal
ENV-A01-MIDA01AMiddle22.4°C48%21.9°C23.0°CNormal
ENV-A01-BOTA01ABottom21.8°C45%21.2°C22.5°CNormal
ENV-A04-TOPA04ATop26.8°C51%23.1°C26.8°CWarning
ENV-B07-MIDB07BMiddle25.3°C53%22.8°C25.6°CWarning
ENV-C04-MIDC04CMiddle24.2°C72%23.5°C24.4°CWarning
ENV-D09-BOTD09DBottomOffline
+121 sensor lainnya
8
Sensor Aktif
0
Kebocoran Aktif
0
Event (30 Hari)
247
Hari Bebas Kebocoran
Semua Sensor Water Leak Normal — DRY
8 sensor aktif di seluruh data hall. Tidak ada kebocoran terdeteksi. Terakhir cek: 00:05 lalu
Lokasi Sensor pada Floor Plan
Row A
A01
A02
A03
A04
A05
CRACW
A06
A07
A08
A09
Row B
B01
B02
B03
B04
B05
CRACW
B06
B07
B08
B09
Row C
C01
C02
C03
C04
CRACW
C05
C06
C07
Row D
D01
D02
D03
D04
D05
CRACW
D06
D07
D08
D09
Sensor WL (Dry)
Sensor WL (Leak)
Status Sensor Water Leak
WL-01 CRAC Row A
Row A · Bawah CRAC-A01 · Floor Level
Dry
WL-02 CRAC Row B
Row B · Bawah CRAC-B01 · Floor Level
Dry
WL-03 CRAC Row C
Row C · Bawah CRAC-C01 · Floor Level
Dry
WL-04 CRAC Row D
Row D · Bawah CRAC-D01 · Floor Level
Dry
WL-05 Cooling Corridor
Corridor · Under Floor
Dry
WL-06 Chiller Room
Mechanical Room · Floor Drain
Dry
WL-07 UPS Room
Electrical Room · Battery Area
Dry
WL-08 Generator Room
Genset Area · Fuel Drain
Dry
Riwayat Event Water Leak
TanggalSensorLokasiDurasiSeverityTindakan
12 Feb 2026 · 03:17WL-05Cooling Corridor00:04:22MinorKondensasi CRAC, dihapus manual
29 Nov 2025 · 14:52WL-01CRAC Row A00:11:08MinorPipa drain CRAC tersumbat, dibersihkan
Tidak ada event lain dalam 365 hari terakhir
40
Total Rack
4 row · 10 rack/row
36
Rack Normal
2
Rack Warning
1
Rack Critical
Floor Plan — Data Hall Lantai 1 (40 Rack)
← Cold Aisle            Row A            Hot Aisle →
A01
A02
A03
A04
A05
CRAC
A06
A07
A08
A09
Row B
B01
B02
B03
B04
B05
CRAC
B06
B07
B08
B09
Row C
C01
C02
C03
C04
CRAC
C05
C06
C07
Row D
D01
D02
D03
D04
D05
CRAC
D06
D07
D08
D09
Normal
Warning
Critical/Alert
CRAC
Maintenance
Kosong
Pilih Rack: Normal
U-Diagram (42U)
SUHU TOP
21.2°C
SUHU MID
22.4°C
SUHU BOT
21.8°C
POWER
4.2 kW
UTILISASI U
67%
PDU
PDU-A01-A/B
Perangkat dalam Rack
UPerangkatTipePowerStatus
78%
Space (Rack)
31/40 rack · 9 tersedia
62%
Power (kW)
247 / 400 kW
62%
Cooling (kW)
312 / 500 kW
68%
U Space (42U)
1142 / 1680 U terisi
+8%
Pertumbuhan/Bulan
Est. penuh: ~3 bulan
Utilisasi Space per Row
Utilisasi Power per Row
Kapasitas Detail per Row
RowRack TotalRack TerisiU TerisiU TotalU %Power UsedPower MaxPower %Cooling UsedStatus
Row A109298420
71%
89 kW100 kW
89%
105 kWWarning
Row B108312420
74%
62 kW100 kW
62%
78 kWNormal
Row C107256420
61%
48 kW100 kW
48%
62 kWNormal
Row D107276420
66%
48 kW100 kW
48%
67 kWNormal
Total403111421680 68% 247 kW400 kW 62% 312 kWNormal