Genset & Backup Power
LIVE
RZ
PLN NORMAL — Semua Genset Standby Ready
4
Total
4
Standby
0
Running
0
Fault
87%
Avg Fuel
GEN-01
Volvo Penta · 2,000 kVA
Standby
0 RPM
Engine
32°C
Coolant
420 kPa
Oil Pres.
248 h
Run Hours
2 h
Next Svc ⚠
Fuel91% · 2,730 L
Health Score
62/100
GEN-02
Cummins · 2,000 kVA
Standby
0 RPM
Engine
31°C
Coolant
415 kPa
Oil Pres.
186 h
Run Hours
64 h
Next Svc
Fuel88% · 2,640 L
Health Score
84/100
GEN-03
Perkins · 1,500 kVA
Standby
0 RPM
Engine
29°C
Coolant
408 kPa
Oil Pres.
142 h
Run Hours
108 h
Next Svc
Fuel85% · 1,700 L
Health Score
91/100
GEN-04
Perkins · 1,500 kVA
Standby
0 RPM
Engine
30°C
Coolant
412 kPa
Oil Pres.
98 h
Run Hours
152 h
Next Svc
Fuel83% · 1,660 L
Health Score
88/100
J1939 Engine Trend — GEN-02 (Last Run: 3 hr lalu)
Run Activity 30 Hari
7
Total Start
18.4 h
Total Hours
284 L
Fuel Used
Alarm Log (30 hari)
WaktuGensetAlarmNilaiDurasiStatus
2026-03-04 14:22GEN-01Service Due Warning248/250 jamOngoingActive
2026-02-28 23:11GEN-02Mains Fail — Auto StartPLN dip 45s14 minResolved
2026-02-22 03:45GEN-01Coolant Temp High96.2°C8 minResolved
2026-02-15 08:00GEN-03Monthly Test RunScheduled PM15 minCompleted
2026-02-10 19:32ALLMains Fail — PLN TripOutage 22 min22 minResolved
Fuel Monitor
Level BBM real-time · Konsumsi · Jadwal pengisian
9,730 L
Total Fuel
Kapasitas: 11,000 L · 88%
284 L
Konsumsi 30hr
~9.5 L/jam saat running
32 hari
Estimasi Habis
Asumsi 2× test run/bulan
1
Pengisian Terjadwal
GEN-04 · 15 Mar 2026
Level Tangki BBM per Genset
GEN-01
Volvo Penta
91%
2,730 / 3,000 L
GEN-02
Cummins
88%
2,640 / 3,000 L
GEN-03
Perkins
85%
1,700 / 2,000 L
GEN-04
Perkins
83%
1,660 / 2,000 L
Konsumsi Fuel 30 Hari
Riwayat Pengisian BBM
TanggalGensetVolumeLevel Sebelum→Sesudah
2026-02-10GEN-01800 L64% → 91%
2026-02-10GEN-02700 L65% → 88%
2026-01-15GEN-03400 L65% → 85%
2026-01-15GEN-04380 L64% → 83%
Jadwal: GEN-04 · 15 Mar 2026 · Est. 400 L
Run History
Riwayat lengkap operasional genset · Emergency / Test / PM
12
Total Start (90hr)
2 Emergency · 5 Test · 5 PM
38.2 h
Total Runtime
Avg per event: 3.2 jam
542 L
Total Fuel Used
Avg: 14.2 L/jam
100%
Success Rate
0 Failed Start
Run Hours per Genset (90 Hari)
Aktivitas Start 90 Hari
Log Operasional
Waktu StartGensetTipeKeteranganDurationFuelMax RPMMax CoolantOperatorStatus
2026-03-05 02:14GEN-02EmergencyPLN Voltage Dip Auto Start14 min22 L1,50288°CAutoOK
2026-03-01 09:00GEN-04PM TestMonthly Scheduled Test Run15 min24 L1,50085°CAhmad S.PASS
2026-02-28 23:11ALLEmergencyPLN Outage — parallel 22 menit22 min128 L1,50191°CAutoOK
2026-02-15 08:00GEN-03PM TestMonthly Scheduled Test Run15 min19 L1,49983°CBudi W.PASS
2026-02-15 08:20GEN-01PM TestMonthly Scheduled Test Run15 min21 L1,50193°CBudi W.Coolant High
2026-01-20 14:30GEN-01Load TestAnnual Full Load Test 100%4 h230 L1,50089°CTim EEPASS