Power Monitoring & PUE
LIVE
RZ
2.84 MW
Total Facility Load
Rated: 4.0 MW · 71% utilized
1.42
PUE Real-time
Target ≤ 1.4 · DCiE: 70.4%
72.3%
UPS Load Avg
48 unit · 1.96 MW output
4,382 kWh
Energy Hari Ini
Est. biaya: Rp 6.2 juta
3
Power Alerts
1 Critical · 2 Warning
PUE Trend 30 Hari
Power Breakdown
2.00 MW
IT Load (70.4%)
0.72 MW
Cooling (25.4%)
0.08 MW
Lighting (2.8%)
0.04 MW
Other (1.4%)
LVMDP Top Consumers
PanelZonakWkWh/hariPF
LVMDP-01Main A842 kW7,8900.94
LVMDP-02Main B798 kW7,4210.93
LVMDP-03Cooling412 kW3,8400.92
LVMDP-04IT Zone A384 kW3,5820.88
LVMDP-05IT Zone B348 kW3,2480.91
+395 panel · Lihat semua →
ATS Status
ATSPosisiSrc ASrc BStatus
ATS-01Src A380.2 VOK
ATS-02Src A379.8 VOK
ATS-03Src A381.1 VOK
ATS-04Src A380.5 VOK
+12 ATS · Lihat semua →
LVMDP Panels
400 rack panels · Total load 2,840 kW
400
Total Panels
395 Normal · 4 Warning · 1 Critical
2,840 kW
Total Active (kW)
Kapasitas 4,000 kW · 71%
628 kVAR
Total Reactive (kVAR)
Apparent: 2,909 kVA
0.972
True PF (Avg)
cos φ avg: 0.985 · Target ≥ 0.90 ✓
2.1%
THD-V Max
Unbalance max: 1.4% · OK
Daftar LVMDP Panel (400 unit)
Diperbarui: 07/03/2026 14:32:15
Panel IDNamaZonakWkVARkVATrue PFcos φkWh Hari IniStatus
LVMDP-01Main Distribution AZone A842.3185.4864.40.9750.9887,890Normal
LVMDP-02Main Distribution BZone B798.1175.8819.20.9740.9877,421Normal
LVMDP-03Cooling DistributionCooling412.889.4422.30.9780.9913,840Normal
LVMDP-04IT Zone A PDU FeedZone A384.298.1397.50.9670.9813,582PF Low
LVMDP-05IT Zone B PDU FeedZone B348.775.2357.70.9750.9883,248Normal
LVMDP-06UPS Bypass AZone A220.447.5225.50.9770.9892,056Normal
LVMDP-07UPS Bypass BZone B218.946.8223.80.9780.9902,041Normal
LVMDP-08Genset Feed BusUtility0.00Standby
LVMDP-09Rack Row A01–A10Zone A387.1105.2401.10.9650.9793,612Overload
LVMDP-10Rack Row A11–A20Zone A302.565.1310.50.9750.9872,823Normal
Menampilkan 10 dari 400 panel · Load lebih banyak →
Load per Zona
Total Load Trend 24 Jam
UPS Management
48 unit · Total kapasitas 8,000 kVA
48
Total UPS
44 Normal · 3 Warn · 1 Critical
72.3%
Rata-rata Load
1.96 MW dari 2.72 MW total
42 min
Avg Runtime
Min: 6 min (UPS-B12 ⚠)
24.8°C
Avg Suhu Baterai
Batas: 35°C
6
PM Terjadwal
Minggu ini: 2 unit
Daftar UPS (48 unit)
NamaBrand / ModelLoad %Out kWOut kVAOut kVAROut PFBat %RuntimeStatus
UPS-A01Eaton 93PM · 200 kVA
68%
136.0145.846.20.933 99%45 minNormal
UPS-A02APC Symmetra · 160 kVA
75%
120.0128.640.80.933 98%38 minNormal
UPS-A03Huawei UPS2000 · 200 kVA
83%
166.0178.056.50.933 96%28 minHigh Load
UPS-B12APC Symmetra · 160 kVA
71%
113.6121.838.70.933 18%6 min ⚠Battery Low
UPS-B01Eaton 93PM · 200 kVA
70%
140.0150.147.60.933 100%52 minNormal
UPS-C04Schneider Galaxy · 250 kVA
78%
195.0209.166.40.933 94%31 minPM Scheduled
Menampilkan 6 dari 48 UPS · Load semua →
Distribusi Load UPS
Distribusi Battery Level
Smart PDU
800 unit · 400 rack × 2 PDU/rack · Total 16,000 outlet
800
Total PDU
795 Online · 5 Offline
15,840
Outlet ON
dari 16,000 total (99%)
7
Overload Outlet
Threshold >16A per outlet
28.3°C
Max PDU Temp
Rata-rata: 24.1°C
68.4%
Avg PDU Load
Per-rack avg 4.8 kW
Rack PDU Grid
Klik PDU untuk detail outlet
PDU-A01-A
Rack A01 · Row A · Sisi Kiri
OK
Load4.8 kW / 7.2 kW
Arus: 12.6A / 12.9A / 12.4A24.2°C
20 outlet · 18 ON · 2 OFF
PDU-A01-B
Rack A01 · Row A · Sisi Kanan
OK
Load4.6 kW / 7.2 kW
Arus: 12.1A / 12.0A / 12.3A23.8°C
20 outlet · 18 ON · 2 OFF
PDU-A05-A
Rack A05 · Row A · Sisi Kiri
Warning
Load6.4 kW / 7.2 kW
Arus: 16.8A / 17.1A / 16.6A27.4°C
20 outlet · 20 ON · C6 overcurrent
PDU-B03-A
Rack B03 · Row B · Sisi Kiri
Critical
Load7.0 kW / 7.2 kW
Arus: 18.4A / 18.7A / 18.2A31.8°C ⚠
20 outlet · 20 ON · C3,C4 overcurrent
PDU-A10-B
Rack A10 · Row A · Sisi Kanan
OK
Load3.2 kW / 7.2 kW
Arus: 8.4A / 8.5A / 8.4A22.1°C
20 outlet · 8 ON · 12 OFF
PDU-C02-A
Rack C02 · Row C · Sisi Kiri
OK
Load5.1 kW / 7.2 kW
Arus: 13.4A / 13.5A / 13.4A25.3°C
20 outlet · 15 ON · 5 OFF
Menampilkan 6 dari 800 PDU · Load lebih banyak →
Load Distribusi per Row
Top 5 PDU Tertinggi
PDURackLoadUtil %Status
PDU-B03-ARack B037.0 kW
Critical
PDU-A05-ARack A056.4 kW
Warning
PDU-D08-BRack D086.1 kW
Warning
PDU-A12-ARack A125.8 kW
Normal
PDU-C07-ARack C075.6 kW
Normal
ATS — Automatic Transfer Switch
16 unit · Transfer time target < 10 ms
16
Total ATS
16 Normal · 0 Fault
16
Source A Active
PLN normal · semua on Src A
380.3 V
Avg Voltage Src A
Range: 378.8–381.5 V
8.2 ms
Last Transfer Time
ATS-07 · 05/03/26 02:14
ATS-01
Normal
Main UPS A1-A4 · Zone A
Source A (Active)
380.2 V
50.1 Hz · 1,248 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 3 · Last: 05/03/26
ATS-02
Normal
Main UPS A5-A8 · Zone A
Source A (Active)
379.8 V
50.0 Hz · 1,182 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 1 · Last: 28/02/26
ATS-03
Normal
Main UPS B1-B4 · Zone B
Source A (Active)
381.1 V
50.0 Hz · 611 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 5 · Last: 01/03/26
ATS-04
Normal
Cooling Distribution · Cooling
Source A (Active)
380.5 V
50.1 Hz · 569 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 2 · Last: 20/02/26
ATS-05
Normal
IT Zone C PDU Feed
Source A (Active)
379.9 V
50.0 Hz · 517 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 0 · Never
ATS-06
Normal
IT Zone D PDU Feed
Source A (Active)
380.7 V
50.1 Hz · 448 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 1 · Last: 15/01/26
ATS-07
Normal
UPS Maintenance Bypass
Source A (Active)
380.1 V
50.0 Hz · 324 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 7 · Last: 05/03/26 · 8.2 ms
ATS-08
Normal
Security & Building Sys
Source A (Active)
381.0 V
50.1 Hz · 182 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 4 · Last: 12/02/26
Riwayat Transfer (30 Hari Terakhir)
ATSWaktuDariKePenyebabDuration (ms)Restorasi
ATS-0705/03/26 02:14:08Src ASrc BPLN Transient Voltage Dip8.202:18:45 (auto)
ATS-0301/03/26 15:22:31Src ASrc BScheduled PLN Maintenance7.818:05:12 (auto)
ATS-0105/03/26 11:30:00Src ASrc BManual Test — NOC Operator9.111:31:22 (manual)
ATS-0812/02/26 08:45:20Src ASrc BPLN Frequency Deviation9.809:12:40 (auto)
PUE Configuration
Konfigurasi perhitungan PUE · Metode pengukuran · Target & threshold
PUE Real-time
1.42
Power Usage Effectiveness
1.35
Best (30hr)
1.40
Target
1.58
Worst (30hr)
Formula Aktif
PUE = Total Facility Power ÷ IT Equipment Power
= 2,840 kW ÷ 2,000 kW = 1.42
Trend PUE 7 Hari
Pengaturan Kalkulasi PUE
Metode IT Load
Sumber data untuk mengukur beban IT. Pengaruhi akurasi PUE secara langsung.
Saat ini: UPS Output — 48 unit · rata-rata error <0.5%

Interval Kalkulasi
Frekuensi pembaruan nilai PUE. Nilai lebih kecil = lebih real-time tapi beban CPU lebih tinggi.

PUE Target
Nilai PUE yang ingin dicapai. Sistem akan memberikan alert jika melebihi threshold.
Target PUE
Warning Threshold
Critical Threshold

Komponen Dieksklusi
Beban yang tidak dihitung dalam total facility power (sesuai TIA-942 / ISO 30134).

Standar Pelaporan
Standar yang digunakan untuk laporan PUE resmi kepada manajemen dan regulator.

Konfigurasi Alert
Pengiriman notifikasi otomatis saat PUE melebihi batas yang ditentukan.
Power Quality Monitoring
THD · Harmonics · Unbalance · Crest Factor — sesuai IEC 61000, IEEE 519
2.1%
THD-V Max
Batas: <5% (IEC 61000-2-2) ✓
19.4%
THD-I Max
LVMDP-09 ⚠ · Batas: <20%
1.8%
V Unbalance Max
Batas: <2% (NEMA MG1) ✓
2.04
Crest Factor Max
PDU-B03-A ⚠ · Normal: 1.414
3
PQ Alerts
1 THD-I · 1 CF High · 1 Unbalance
THD per Panel (Top 8)
Crest Factor per PDU
Ringkasan Power Quality per Device
DeviceTipeTrue PFcos φ (DPF)THD-V max%THD-I max%V UnbalanceI UnbalanceCrest FactorStatus PQ
LVMDP-01LVMDP0.9750.9882.3%9.1%0.3%1.4%N/AOK
LVMDP-02LVMDP0.9740.9872.0%8.2%0.4%1.1%N/AOK
LVMDP-04LVMDP0.9670.9813.3%15.1%0.7%3.8%N/ATHD-I High
LVMDP-09LVMDP0.9650.9794.5%19.4%1.8%8.2%N/ATHD-I Critical
PDU-A01-APDU Smart0.9300.952N/AN/AN/AN/A1.52OK
PDU-A01-BPDU Metered0.940N/AN/AN/AN/AN/AN/AOK
PDU-A05-APDU Smart0.9100.934N/AN/AN/AN/A1.84CF High
PDU-B03-APDU Smart0.8900.918N/AN/AN/AN/A2.04CF Critical
N/A = parameter tidak didukung oleh tier device tersebut. LVMDP tidak support Crest Factor. Metered PDU tidak support cos φ / CF.
Harmonics 3rd/5th/7th (LVMDP-09)
⚠ Critical
3rd harmonic (150Hz): neutral overloading · 5th (250Hz): transformer heating · 7th (350Hz): motor losses
Standar & Batas Referensi
ParameterBatas NormalStandarStatus Saat Ini
THD-V< 5%IEC 61000-2-22.1% ✓
THD-I< 20%IEC 61000-3-219.4% ⚠
V Unbalance< 2%NEMA MG11.8% ✓
I Unbalance< 10%Recommended8.2% ✓
Crest Factor< 1.8Practical2.04 ⚠
True PF≥ 0.90PLN Contract0.972 ✓