2.84 MW
Total Facility Load
Rated: 4.0 MW · 71% utilized
1.42
PUE Real-time
Target ≤ 1.4 · DCiE: 70.4%
72.3%
UPS Load Avg
48 unit · 1.96 MW output
4,382 kWh
Energy Hari Ini
Est. biaya: Rp 6.2 juta
3
Power Alerts
1 Critical · 2 Warning
PUE Trend 30 Hari
Power Breakdown
2.00 MW
IT Load (70.4%)
0.72 MW
Cooling (25.4%)
0.08 MW
Lighting (2.8%)
0.04 MW
Other (1.4%)
LVMDP Top Consumers
| Panel | Zona | kW | kWh/hari | PF |
|---|---|---|---|---|
| LVMDP-01 | Main A | 842 kW | 7,890 | 0.94 |
| LVMDP-02 | Main B | 798 kW | 7,421 | 0.93 |
| LVMDP-03 | Cooling | 412 kW | 3,840 | 0.92 |
| LVMDP-04 | IT Zone A | 384 kW | 3,582 | 0.88 |
| LVMDP-05 | IT Zone B | 348 kW | 3,248 | 0.91 |
| +395 panel · Lihat semua → | ||||
ATS Status
| ATS | Posisi | Src A | Src B | Status |
|---|---|---|---|---|
| ATS-01 | Src A | 380.2 V | — | OK |
| ATS-02 | Src A | 379.8 V | — | OK |
| ATS-03 | Src A | 381.1 V | — | OK |
| ATS-04 | Src A | 380.5 V | — | OK |
| +12 ATS · Lihat semua → | ||||
LVMDP Panels
400 rack panels · Total load 2,840 kW
400
Total Panels
395 Normal · 4 Warning · 1 Critical
2,840 kW
Total Active (kW)
Kapasitas 4,000 kW · 71%
628 kVAR
Total Reactive (kVAR)
Apparent: 2,909 kVA
0.972
True PF (Avg)
cos φ avg: 0.985 · Target ≥ 0.90 ✓
2.1%
THD-V Max
Unbalance max: 1.4% · OK
Daftar LVMDP Panel (400 unit)
Diperbarui: 07/03/2026 14:32:15
| Panel ID | Nama | Zona | kW | kVAR | kVA | True PF | cos φ | kWh Hari Ini | Status |
|---|---|---|---|---|---|---|---|---|---|
| LVMDP-01 | Main Distribution A | Zone A | 842.3 | 185.4 | 864.4 | 0.975 | 0.988 | 7,890 | Normal |
| LVMDP-02 | Main Distribution B | Zone B | 798.1 | 175.8 | 819.2 | 0.974 | 0.987 | 7,421 | Normal |
| LVMDP-03 | Cooling Distribution | Cooling | 412.8 | 89.4 | 422.3 | 0.978 | 0.991 | 3,840 | Normal |
| LVMDP-04 | IT Zone A PDU Feed | Zone A | 384.2 | 98.1 | 397.5 | 0.967 | 0.981 | 3,582 | PF Low |
| LVMDP-05 | IT Zone B PDU Feed | Zone B | 348.7 | 75.2 | 357.7 | 0.975 | 0.988 | 3,248 | Normal |
| LVMDP-06 | UPS Bypass A | Zone A | 220.4 | 47.5 | 225.5 | 0.977 | 0.989 | 2,056 | Normal |
| LVMDP-07 | UPS Bypass B | Zone B | 218.9 | 46.8 | 223.8 | 0.978 | 0.990 | 2,041 | Normal |
| LVMDP-08 | Genset Feed Bus | Utility | 0.0 | — | — | — | — | 0 | Standby |
| LVMDP-09 | Rack Row A01–A10 | Zone A | 387.1 | 105.2 | 401.1 | 0.965 | 0.979 | 3,612 | Overload |
| LVMDP-10 | Rack Row A11–A20 | Zone A | 302.5 | 65.1 | 310.5 | 0.975 | 0.987 | 2,823 | Normal |
| Menampilkan 10 dari 400 panel · Load lebih banyak → | |||||||||
Load per Zona
Total Load Trend 24 Jam
UPS Management
48 unit · Total kapasitas 8,000 kVA
48
Total UPS
44 Normal · 3 Warn · 1 Critical
72.3%
Rata-rata Load
1.96 MW dari 2.72 MW total
42 min
Avg Runtime
Min: 6 min (UPS-B12 ⚠)
24.8°C
Avg Suhu Baterai
Batas: 35°C
6
PM Terjadwal
Minggu ini: 2 unit
Daftar UPS (48 unit)
| Nama | Brand / Model | Load % | Out kW | Out kVA | Out kVAR | Out PF | Bat % | Runtime | Status |
|---|---|---|---|---|---|---|---|---|---|
| UPS-A01 | Eaton 93PM · 200 kVA | 68% |
136.0 | 145.8 | 46.2 | 0.933 | 99% | 45 min | Normal |
| UPS-A02 | APC Symmetra · 160 kVA | 75% |
120.0 | 128.6 | 40.8 | 0.933 | 98% | 38 min | Normal |
| UPS-A03 | Huawei UPS2000 · 200 kVA | 83% |
166.0 | 178.0 | 56.5 | 0.933 | 96% | 28 min | High Load |
| UPS-B12 | APC Symmetra · 160 kVA | 71% |
113.6 | 121.8 | 38.7 | 0.933 | 18% | 6 min ⚠ | Battery Low |
| UPS-B01 | Eaton 93PM · 200 kVA | 70% |
140.0 | 150.1 | 47.6 | 0.933 | 100% | 52 min | Normal |
| UPS-C04 | Schneider Galaxy · 250 kVA | 78% |
195.0 | 209.1 | 66.4 | 0.933 | 94% | 31 min | PM Scheduled |
| Menampilkan 6 dari 48 UPS · Load semua → | |||||||||
Distribusi Load UPS
Distribusi Battery Level
Smart PDU
800 unit · 400 rack × 2 PDU/rack · Total 16,000 outlet
800
Total PDU
795 Online · 5 Offline
15,840
Outlet ON
dari 16,000 total (99%)
7
Overload Outlet
Threshold >16A per outlet
28.3°C
Max PDU Temp
Rata-rata: 24.1°C
68.4%
Avg PDU Load
Per-rack avg 4.8 kW
Rack PDU Grid
Klik PDU untuk detail outlet
PDU-A01-A
Rack A01 · Row A · Sisi Kiri
Load4.8 kW / 7.2 kW
Arus: 12.6A / 12.9A / 12.4A24.2°C
20 outlet · 18 ON · 2 OFF
PDU-A01-B
Rack A01 · Row A · Sisi Kanan
Load4.6 kW / 7.2 kW
Arus: 12.1A / 12.0A / 12.3A23.8°C
20 outlet · 18 ON · 2 OFF
PDU-A05-A
Rack A05 · Row A · Sisi Kiri
Load6.4 kW / 7.2 kW
Arus: 16.8A / 17.1A / 16.6A27.4°C
20 outlet · 20 ON · C6 overcurrent
PDU-B03-A
Rack B03 · Row B · Sisi Kiri
Load7.0 kW / 7.2 kW
Arus: 18.4A / 18.7A / 18.2A31.8°C ⚠
20 outlet · 20 ON · C3,C4 overcurrent
PDU-A10-B
Rack A10 · Row A · Sisi Kanan
Load3.2 kW / 7.2 kW
Arus: 8.4A / 8.5A / 8.4A22.1°C
20 outlet · 8 ON · 12 OFF
PDU-C02-A
Rack C02 · Row C · Sisi Kiri
Load5.1 kW / 7.2 kW
Arus: 13.4A / 13.5A / 13.4A25.3°C
20 outlet · 15 ON · 5 OFF
Menampilkan 6 dari 800 PDU · Load lebih banyak →
Load Distribusi per Row
Top 5 PDU Tertinggi
| PDU | Rack | Load | Util % | Status |
|---|---|---|---|---|
| PDU-B03-A | Rack B03 | 7.0 kW | Critical | |
| PDU-A05-A | Rack A05 | 6.4 kW | Warning | |
| PDU-D08-B | Rack D08 | 6.1 kW | Warning | |
| PDU-A12-A | Rack A12 | 5.8 kW | Normal | |
| PDU-C07-A | Rack C07 | 5.6 kW | Normal |
ATS — Automatic Transfer Switch
16 unit · Transfer time target < 10 ms
16
Total ATS
16 Normal · 0 Fault
16
Source A Active
PLN normal · semua on Src A
380.3 V
Avg Voltage Src A
Range: 378.8–381.5 V
8.2 ms
Last Transfer Time
ATS-07 · 05/03/26 02:14
ATS-01
NormalMain UPS A1-A4 · Zone A
Source A (Active)
380.2 V
50.1 Hz · 1,248 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 3 · Last: 05/03/26
ATS-02
NormalMain UPS A5-A8 · Zone A
Source A (Active)
379.8 V
50.0 Hz · 1,182 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 1 · Last: 28/02/26
ATS-03
NormalMain UPS B1-B4 · Zone B
Source A (Active)
381.1 V
50.0 Hz · 611 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 5 · Last: 01/03/26
ATS-04
NormalCooling Distribution · Cooling
Source A (Active)
380.5 V
50.1 Hz · 569 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 2 · Last: 20/02/26
ATS-05
NormalIT Zone C PDU Feed
Source A (Active)
379.9 V
50.0 Hz · 517 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 0 · Never
ATS-06
NormalIT Zone D PDU Feed
Source A (Active)
380.7 V
50.1 Hz · 448 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 1 · Last: 15/01/26
ATS-07
NormalUPS Maintenance Bypass
Source A (Active)
380.1 V
50.0 Hz · 324 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 7 · Last: 05/03/26 · 8.2 ms
ATS-08
NormalSecurity & Building Sys
Source A (Active)
381.0 V
50.1 Hz · 182 A
Source B (Standby)
— V
Genset · Ready
Transfer count: 4 · Last: 12/02/26
Riwayat Transfer (30 Hari Terakhir)
| ATS | Waktu | Dari | Ke | Penyebab | Duration (ms) | Restorasi |
|---|---|---|---|---|---|---|
| ATS-07 | 05/03/26 02:14:08 | Src A | Src B | PLN Transient Voltage Dip | 8.2 | 02:18:45 (auto) |
| ATS-03 | 01/03/26 15:22:31 | Src A | Src B | Scheduled PLN Maintenance | 7.8 | 18:05:12 (auto) |
| ATS-01 | 05/03/26 11:30:00 | Src A | Src B | Manual Test — NOC Operator | 9.1 | 11:31:22 (manual) |
| ATS-08 | 12/02/26 08:45:20 | Src A | Src B | PLN Frequency Deviation | 9.8 | 09:12:40 (auto) |
PUE Configuration
Konfigurasi perhitungan PUE · Metode pengukuran · Target & threshold
PUE Real-time
1.42
Power Usage Effectiveness
1.35
Best (30hr)
1.40
Target
1.58
Worst (30hr)
Formula Aktif
PUE = Total Facility Power ÷ IT Equipment Power
= 2,840 kW ÷ 2,000 kW = 1.42
Trend PUE 7 Hari
Pengaturan Kalkulasi PUE
Metode IT Load
Sumber data untuk mengukur beban IT. Pengaruhi akurasi PUE secara langsung.
Saat ini: UPS Output — 48 unit · rata-rata error <0.5%
Interval Kalkulasi
Frekuensi pembaruan nilai PUE. Nilai lebih kecil = lebih real-time tapi beban CPU lebih tinggi.
PUE Target
Nilai PUE yang ingin dicapai. Sistem akan memberikan alert jika melebihi threshold.
Target PUE
Warning Threshold
Critical Threshold
Komponen Dieksklusi
Beban yang tidak dihitung dalam total facility power (sesuai TIA-942 / ISO 30134).
Standar Pelaporan
Standar yang digunakan untuk laporan PUE resmi kepada manajemen dan regulator.
Konfigurasi Alert
Pengiriman notifikasi otomatis saat PUE melebihi batas yang ditentukan.
Power Quality Monitoring
THD · Harmonics · Unbalance · Crest Factor — sesuai IEC 61000, IEEE 519
2.1%
THD-V Max
Batas: <5% (IEC 61000-2-2) ✓
19.4%
THD-I Max
LVMDP-09 ⚠ · Batas: <20%
1.8%
V Unbalance Max
Batas: <2% (NEMA MG1) ✓
2.04
Crest Factor Max
PDU-B03-A ⚠ · Normal: 1.414
3
PQ Alerts
1 THD-I · 1 CF High · 1 Unbalance
THD per Panel (Top 8)
Crest Factor per PDU
Ringkasan Power Quality per Device
| Device | Tipe | True PF | cos φ (DPF) | THD-V max% | THD-I max% | V Unbalance | I Unbalance | Crest Factor | Status PQ |
|---|---|---|---|---|---|---|---|---|---|
| LVMDP-01 | LVMDP | 0.975 | 0.988 | 2.3% | 9.1% | 0.3% | 1.4% | N/A | OK |
| LVMDP-02 | LVMDP | 0.974 | 0.987 | 2.0% | 8.2% | 0.4% | 1.1% | N/A | OK |
| LVMDP-04 | LVMDP | 0.967 | 0.981 | 3.3% | 15.1% | 0.7% | 3.8% | N/A | THD-I High |
| LVMDP-09 | LVMDP | 0.965 | 0.979 | 4.5% | 19.4% | 1.8% | 8.2% | N/A | THD-I Critical |
| PDU-A01-A | PDU Smart | 0.930 | 0.952 | N/A | N/A | N/A | N/A | 1.52 | OK |
| PDU-A01-B | PDU Metered | 0.940 | N/A | N/A | N/A | N/A | N/A | N/A | OK |
| PDU-A05-A | PDU Smart | 0.910 | 0.934 | N/A | N/A | N/A | N/A | 1.84 | CF High |
| PDU-B03-A | PDU Smart | 0.890 | 0.918 | N/A | N/A | N/A | N/A | 2.04 | CF Critical |
N/A = parameter tidak didukung oleh tier device tersebut. LVMDP tidak support Crest Factor. Metered PDU tidak support cos φ / CF.
Harmonics 3rd/5th/7th (LVMDP-09)
⚠ Critical3rd harmonic (150Hz): neutral overloading · 5th (250Hz): transformer heating · 7th (350Hz): motor losses
Standar & Batas Referensi
| Parameter | Batas Normal | Standar | Status Saat Ini |
|---|---|---|---|
| THD-V | < 5% | IEC 61000-2-2 | 2.1% ✓ |
| THD-I | < 20% | IEC 61000-3-2 | 19.4% ⚠ |
| V Unbalance | < 2% | NEMA MG1 | 1.8% ✓ |
| I Unbalance | < 10% | Recommended | 8.2% ✓ |
| Crest Factor | < 1.8 | Practical | 2.04 ⚠ |
| True PF | ≥ 0.90 | PLN Contract | 0.972 ✓ |